Downloads :      Leaflet   |   Manual
Higher Capacity
   
   

Powering the lifelines of the nation, Luminous offers customized energy solution package to keep the essential entities of the corporate behemoth on its feet irrelevant of the irregular energy supplies, whether it is a petrol pump or a big corporate office. These inverters / long back up UPS are specially designed to give convenience, comfort and safe power for smooth running of even petrol pumps/gas stations/big offices. These products are preferred over generators since they offer multiple advantages over conventional generators. Available in a wide range, this range is highly suitable for most expensive and sophisticated equipments.


Features & Protection

  • Digital signal processing technology
  • Smart charge plus technology for faster charging and longer battery life
  • Intelligent thermal management for longer life and higher reliability
  • High frequency based design for instantaneous sine wave control
  • Regulated battery charging from 150V to 280V
  • Audio alarm on: battery low pre-alarm, overload & short circuit trip
  • Display for mains on, UPS on, overload/short circuit trip, battery low trip and battery reverse connection

    3 KVA 5KVA  6KVA  10KVA
Input Undervoltage  140 +/- 5 V
Undervoltage Restoration  150 +/- 5 V
Overvoltage  280 +/- 5 V
Overvoltage Restoration  270 +/- 5 V
Output Maximum Power  3 KVA 5KVA  6KVA  10KVA
Voltage (INVERTER Mode)  230 V Nominal
Voltage (Mains Mode)  Same as Input
Frequency (INVERTER Mode)  50 Hz. +/- 0.5 Hz.
Frequency (Mains Mode)  Same as Input (45-55 Hz.)
Overload  > 100 %
Battery Type  120 AH- 150AH Lead Acid Type
Number  4 8 10 15
Typical Recharge Time  10-12 Hrs.
Protection  Low Battery, Reverse Polarity
Physical Net Weight (Kg.)       61 81
Gross Weight(Kg.)(approx.)       77.6 88.1
Dimension(LxWxH) mm (approx.)       390 x 160 x 390  410x630x700
LED Display Input Under Voltage  MAINS LOW
Input Over Voltage  MAINS HI
Low Batery Pre-Alarm  CAUTION LOW BATTERY
Battery Low  TRIP BATTERY LOW
Overload  TRIP OVER LOAD
Short Circuit in Inverter Mode  SHORT CIRCUIT
Short Circuit in Mains Mode  INPUT MCB TRIP
Input MCB Trip  INPUT MCB TRIP
Over Temperature  THERMAL SHUTDOWN
Alarms Low Battery Pre-Alarm  One Beep every 10 seconds
Low Battery  Continuous
Overload  Continuous
Over Temperature  Five Beeps every 5 seconds
Mains MCB Trip  One Beep every 12 minutes
Short circuit  Continuous
Environmental Operating Temperature  0-40o C  (32-104 o  F)
Storage Temperature  0-40o C  (32-104 o  F)
Humidity  0-95 % RH non -condensing